About the Voltage Drop Calculator
Long cable runs lose voltage along the way, which can make motors overheat, lights dim and electronics misbehave. This voltage drop calculator works out the drop and the percentage drop from the cable material, size in AWG or mm², one-way length, current and supply voltage, for DC and AC circuits. Many guidelines aim to keep the drop within a few percent; if it is too high, a thicker cable or a shorter run reduces it. Wiring regulations differ between countries, so final cable sizes should be confirmed by a qualified electrician.
The resistance of each conductor is R = ρL ÷ A, where ρ is the resistivity of the metal, L the length and A the cross-sectional area. For DC and single-phase circuits the current flows out and back, so the drop is 2 × I × R; for balanced three-phase circuits it is √3 × I × R. Copper's resistivity is about 0.01724 Ω·mm²/m at 20 °C and aluminum's about 0.0282, and both rise as the cable warms up, which the 75 °C option accounts for.
Example: a 30 m run of 2.5 mm² copper cable carrying 16 A on a 230 V single-phase circuit has about 0.207 Ω per conductor, so it drops 2 × 16 × 0.207 ≈ 6.62 V, about 2.88%, leaving 223.4 V at the load. A common design guide is to keep the drop under about 3% on branch circuits and 5% overall; local electrical codes set the actual limits.
This calculator ignores reactance, which matters only for very large cables. For power and current from appliance ratings use the watts volts amps calculator, for gauge sizes the AWG to mm converter, and for basic relationships the Ohm's law calculator.
How to use the Voltage Drop Calculator
- Choose the conductorCopper or aluminum, and the operating temperature.
- Choose the cable sizePick an AWG gauge or a metric size in mm².
- Enter the circuitSupply voltage, current, one-way length and circuit type.
- Read the dropSee the voltage drop, the percent drop and the voltage at the load.
Voltage Drop Calculator features
- Copper and aluminum conductors
- AWG gauges and metric mm² sizes
- DC, single-phase and three-phase
- Percent drop and load voltage
- 20 °C and 75 °C resistivity
- Length in meters or feet
- Cable resistance shown
Common uses
- Choosing cable sizes for long runs
- Garden lighting and outbuilding supplies
- Solar panel and battery wiring
- EV charger and workshop circuits
- Low-voltage LED installations
Voltage drop in practice: water pumps, long service cables, low-voltage solar and choosing cable sizes
Every cable has resistance, so some voltage is lost along its length. On a short run the loss is negligible, but long cables to pumps, outbuildings or solar panels can lose enough voltage to make motors struggle, lights dim and inverters shut down. This guide works through a water pump on a long cable, explains why low-voltage solar systems are so sensitive, compares copper and aluminium and gives practical rules for choosing cable sizes.
A worked example: a water pump 40 metres away
A 1.5 kW pump with a power factor of about 0.85 on a 230 V supply draws about 7.7 A. With 40 metres of 2.5 mm² copper cable, each conductor has a resistance of about 0.28 Ω, and the round trip drops about 4.3 V, roughly 1.9%. With 1.5 mm² cable instead, the drop rises to about 7.2 V, around 3.1%.
The thinner cable might seem adequate, but motors draw much more current when starting, and the voltage dip at start-up is several times larger. Pumps fed through long, thin cables often struggle to start, overheat or fail early.
Low voltage from the grid
In many areas, the voltage arriving at homes is already below the nominal 230 V, especially at peak times and at the far end of long distribution lines. Any further drop inside the house adds to the problem. Thicker cables for heavy loads, and voltage stabilisers for sensitive equipment where supply voltage is poor, help appliances work properly.
Low-voltage solar systems
Voltage drop matters most in low-voltage systems. A 12 V solar or battery system carrying 20 A through 5 metres of 4 mm² cable, 10 metres there and back, loses about 0.9 V, more than 7% of the voltage. The same power at 48 V needs only a quarter of the current and loses a sixteenth as much power in the cable. This is why larger solar systems use 24 V or 48 V batteries, or high-voltage panel strings.
Copper and aluminium
Aluminium has a resistivity about 1.6 times that of copper, so an aluminium cable needs a larger cross-section to carry the same current with the same drop. Aluminium is cheaper and lighter, which is why it is common for overhead lines and large feeders, but connections need suitable fittings to avoid overheating where aluminium meets copper.
Acceptable limits
A widely used design guide limits voltage drop to about 3% on lighting circuits and 5% on other circuits, from the supply to the load, though local regulations vary. Motor circuits and sensitive electronics benefit from staying well within these limits, particularly where the incoming supply voltage is already low.
Choosing a cable
Cable size must satisfy two separate checks: the current-carrying capacity, so the cable does not overheat, and the voltage drop, so the load receives enough voltage. On short runs, current capacity usually decides the size; on long runs, voltage drop often requires a thicker cable than current alone would suggest.
Spotting voltage drop
Lights that dim when a pump or air conditioner starts, motors that hum without turning and inverters that show low-voltage alarms all suggest excessive voltage drop or a poor connection. A loose or corroded terminal adds resistance just like a long cable, and it can become hot, so such symptoms should be checked by an electrician.
Common mistakes
- Using the one-way length instead of the round trip for single-phase and DC circuits.
- Sizing cables for running current only and ignoring motor starting.
- Using thin cables in low-voltage solar systems.
- Joining aluminium and copper without suitable connectors.
Related tools
To convert between wire gauges and mm², use AWG to mm Converter. For basic electrical relationships, try Ohm's Law Calculator, and to convert watts to amps, Watts Volts Amps Calculator.
Extension leads
Long, thin extension leads cause voltage drop too. Running a power tool or heater on a 30-metre lead with thin conductors can reduce its performance and make the lead warm. For long runs, use heavy-duty leads with thicker conductors, unroll cable drums fully to avoid heating and keep the load within the lead's rating.
Lights at the end of long runs
Garden lights, gate lights and outbuildings at the end of long cables can appear dim because of voltage drop. LED lights tolerate lower voltage better than older lamps, but their drivers may flicker if the voltage falls too far. A thicker cable for the run, or a supply placed closer, solves the problem.
Voltage drop and wasted energy
Voltage drop also means energy lost as heat in the cable. A cable losing 3% of its voltage at full load wastes roughly 3% of the power delivered. On a heavily used circuit, such as a pump running many hours a day, a thicker cable can pay for itself over time through lower losses.
Limits
The calculator uses standard resistivity values at typical temperatures. Final cable sizing should follow local wiring regulations and an electrician's judgement.
Frequently asked questions
What is voltage drop?
The loss of voltage along a cable caused by its resistance. The longer and thinner the cable, and the higher the current, the more voltage is lost before it reaches the equipment.
How do I calculate voltage drop?
For DC or single-phase circuits, Vdrop = 2 × I × ρ × L ÷ A, using the one-way length L. For three-phase, replace 2 with √3. The calculator handles units and resistivity for you.
What is an acceptable voltage drop?
A common guideline is no more than 3% on a branch circuit and 5% in total from the supply to the load. Some codes and equipment manufacturers set stricter limits.
Why does length matter so much?
Resistance grows in direct proportion to length, so doubling the run doubles the voltage drop. For long runs, a thicker cable is the usual fix.
Should I use one-way or round-trip length?
Enter the one-way length from the supply to the load. The calculator doubles it for DC and single-phase circuits, because current flows out and back.
Why is aluminum cable thicker for the same job?
Aluminum has about 1.6 times the resistivity of copper, so an aluminum conductor needs roughly 1.6 times the cross-sectional area to give the same voltage drop.
Does temperature affect voltage drop?
Yes. Metal resistance rises about 0.4% per °C for copper, so a cable at 75 °C has around 22% more resistance than at 20 °C. Use the 75 °C option for cables running near full load.
Does voltage drop matter more on low-voltage systems?
Yes. A 1 V drop is under 0.5% on 230 V but over 8% on a 12 V system, which is why 12 V and 24 V wiring for boats, vehicles and solar needs much thicker cable.