About the AWG to mm Converter
Wire sizes are given in American Wire Gauge on many cables and components, while metric countries use cross-sectional area in square millimeters. This AWG to mm converter translates any gauge from 0000 to 40 into diameter in millimeters and inches, area in mm² and kcmil, and resistance per length, and converts metric sizes back to the nearest gauge: 12 AWG is about 2.05 mm across, roughly 3.31 mm². Remember that AWG numbers run backwards, so a smaller number means a thicker wire.
AWG sizes follow a geometric series defined by the formula d = 0.127 mm × 92^((36 − n) ÷ 39), where n is the gauge number and 0000 counts as −3. Every 6 gauges halves the diameter, and every 3 gauges roughly halves the cross-sectional area, which doubles the resistance. Smaller gauge numbers mean thicker wire. Metric cable is sold by cross-section in mm², so the area is the figure to compare when matching an AWG cable to a metric one.
Example: 12 AWG wire is about 2.053 mm across with a cross-section of about 3.309 mm², close to the 4 mm² metric size but larger than 2.5 mm². 10 AWG is 2.588 mm and 5.261 mm². 0 AWG is 8.251 mm, and 0000 AWG is exactly 0.46 inches, 11.684 mm. A 2.0 mm diameter wire is between 12 and 13 AWG, nearest 12.
Thicker wire carries more current with less voltage drop. Check a cable run with the voltage drop calculator, estimate loads with the watts volts amps calculator, and convert other lengths with the length converter.
How to use the AWG to mm Converter
- Choose the directionAWG to metric, diameter to AWG, or area to AWG.
- Pick or type the sizeSelect a gauge, or type a diameter in mm or an area in mm².
- Read the conversionSee diameter, area, kcmil and resistance.
- Check the chartCompare neighboring gauges in the AWG table.
AWG to mm Converter features
- AWG 0000 to 40
- Diameter in mm and inches
- Cross-section in mm² and kcmil
- Copper resistance per km and per 1,000 ft
- Diameter or area back to the nearest AWG
- Full AWG chart
- Exact AWG formula
Common uses
- Matching US and metric cables
- Electronics and hobby wiring
- Speaker and audio cable choice
- Automotive and marine wiring
- Electrical homework
Wire sizes in practice: AWG, mm² and the 7/29-style cables sold in Pakistan
Wire sizes come in several systems, and buyers in Pakistan often meet three of them in one week: American Wire Gauge on imported electronics and network cables, metric square millimetres on international specifications and local strand designations such as 7/29 or 7/36 at electrical shops. This guide works through these systems, explains how to compare them, gives typical uses for common sizes and shows how to spot undersized or fake cables.
A worked example: local strand sizes
Cables in Pakistan are often sold by strand count and strand diameter in thousandths of an inch. A 7/29 cable has seven strands each 0.029 inches, about 0.74 mm, across. Its total copper area is about 2.98 mm², a little more than the metric 2.5 mm² size. Similar calculations give:
- 3/29: about 1.28 mm².
- 7/36: about 4.60 mm².
- 7/44: about 6.87 mm².
- 7/52: about 9.59 mm².
- 7/64: about 14.5 mm².
These are commonly matched with the nearest metric sizes of 1.5, 2.5, 4, 6, 10 and 16 mm², which helps when comparing local cables with international specifications.
Typical household uses
As a rough guide, smaller cables such as 1.5 mm² or 3/29 serve lighting circuits, 2.5 mm² or 7/29 serve general socket circuits, and 4 to 6 mm², or 7/36 and 7/44, serve air conditioners, water heaters and other heavy loads. Main supply cables are larger still. The correct size depends on the load, the length of the run and how the cable is installed, so an electrician should confirm sizes for each circuit.
AWG on imported products
American Wire Gauge appears on network cables, speaker wire and electronics. Network cables typically use 23 or 24 AWG conductors, and hobby jumper wires are often 22 AWG. In AWG, a smaller number means a thicker wire, and every six gauges roughly halves the diameter, so 12 AWG is about twice the diameter of 18 AWG.
Copper-clad aluminium
Some cheap cables, particularly network cables, use aluminium coated with a thin layer of copper, sold as copper-clad aluminium or CCA. They look like copper but have higher resistance and are more fragile. For network runs, power over Ethernet and anything carrying significant current, solid copper cables are the safer choice. Scratching a conductor end reveals silver-coloured aluminium beneath a CCA coating.
Spotting undersized cable
Some cables are sold with a stated size that their copper does not match. Measuring the diameter of a single strand with a micrometer or vernier calliper, counting the strands and calculating the area reveals the truth. Undersized cables run hotter and drop more voltage than expected, which can cause failures and fire risk.
Stranded and solid wire
Fixed household wiring may use solid or stranded conductors, while flexible cords for appliances always use many fine strands. Stranded wire of the same area carries the same current but is easier to bend. When stripping stranded wire, avoid cutting strands, since each lost strand reduces the effective size.
Insulation and ratings
Besides copper area, a cable's insulation rating matters: voltage rating, temperature rating and suitability for outdoor or underground use. Cables exposed to sunlight need UV-resistant insulation, and cables for solar panels are designed for high DC voltages and heat.
Common mistakes
- Assuming a higher AWG number means a thicker wire.
- Buying cable by name without checking its actual copper area.
- Using copper-clad aluminium for power or long network runs.
- Sizing cable without considering run length and voltage drop.
Related tools
To check voltage drop on a long run, use Voltage Drop Calculator. For current and resistance, try Ohm's Law Calculator, and to convert inches and millimetres, Length Converter.
Cables for solar systems
Solar installations use special DC cables, commonly 4 or 6 mm², designed for outdoor exposure, high temperatures and UV light. Ordinary household cable run across rooftops becomes brittle within a few summers. Matching cable size to the current and length also keeps voltage drop and losses low.
Earth conductors
Earth wires carry fault current so that protective devices trip, so they must be large enough for the circuit they protect. In many installations, the earth conductor is the same size as, or slightly smaller than, the live conductors, according to wiring rules. A missing or undersized earth is a serious safety hazard, especially with metal-bodied appliances.
Buying cable
Buying from reputable brands and dealers, checking the markings on the insulation and keeping receipts make it easier to trace problems later. For a new house, choosing generous cable sizes from the start costs little extra and avoids rewiring when heavier appliances, such as more air conditioners, are added later.
Telephone and alarm wiring
Low-voltage cables for telephones, alarms and doorbells use thin conductors, often around 0.5 mm in diameter, because they carry tiny currents. They should never be used for mains power, even for small loads, because neither their insulation nor their conductor size is designed for it.
Limits
Conversions use standard formulas. Current-carrying capacity depends on installation conditions, so follow local wiring regulations.
Frequently asked questions
How do I convert AWG to mm?
Use d = 0.127 × 92^((36 − n) ÷ 39) mm, where n is the gauge. For 12 AWG that gives 2.053 mm. The calculator also gives the area in mm², which is how metric cable is sized.
What is 12 AWG in mm²?
About 3.31 mm². The nearest common metric sizes are 2.5 mm², which is smaller, and 4 mm², which is larger, so 4 mm² is the safe metric substitute.
Why does a smaller AWG number mean a thicker wire?
The numbers originally counted how many times wire was drawn through dies to make it thinner. More drawing steps gave a higher number and a thinner wire.
How much thicker is each gauge?
Each step down in gauge increases the diameter by about 12.3%. Six gauges double the diameter, and three gauges roughly double the cross-sectional area.
What are 0000, 000, 00 and 0 AWG?
Gauges thicker than 1 AWG, also written 4/0, 3/0, 2/0 and 1/0. 4/0 AWG is exactly 0.46 inches, 11.684 mm, in diameter, the largest standard AWG size.
What is kcmil?
Thousands of circular mils, an area unit used for cables larger than 4/0 AWG. One circular mil is the area of a circle 0.001 inch in diameter, and 1 kcmil is about 0.5067 mm².
Does stranded wire have the same gauge as solid wire?
The gauge refers to the equivalent copper cross-section, so stranded wire of the same gauge is slightly larger in overall diameter because of gaps between strands.
How much current can a wire carry?
It depends on insulation, temperature rating, bundling and installation, so it is set by electrical codes and manufacturer tables rather than by gauge alone. Always check the applicable code.