Watts Volts Amps Calculator

Convert between watts, volts and amps for DC and AC circuits.

Watts Volts Amps Calculator tool

Find
—
Real power
—
Current
—
Voltage
—
Apparent power
—
Equivalent resistance (DC)

About the Watts Volts Amps Calculator

Choosing a fuse, sizing a generator or checking a circuit breaker means converting between watts, volts and amps. This watts volts amps calculator handles DC, single-phase AC such as household supplies and three-phase AC for motors and commercial loads, with power factor where it applies: a 230 V appliance drawing 5 A uses 1,150 W. Electrical work on mains supplies should always be checked by a qualified electrician.

AC circuits add the power factor, the ratio of real power that does useful work to the apparent power the supply delivers. For single-phase AC, P = V × I × PF; for three-phase AC with line-to-line voltage, P = √3 × V × I × PF. Purely resistive loads such as heaters have a power factor of 1, while motors and many power supplies are typically 0.7 to 0.95. Apparent power, S = V × I (× √3 for three phase), sizes cables, fuses and generators.

Example: a 12 V DC device drawing 5 A uses 60 W. A 230 V kettle drawing 10 A at power factor 1 uses 2,300 W, while a 230 V single-phase motor drawing 10 A at power factor 0.9 uses 2,070 W of real power. A three-phase motor on 400 V drawing 10 A at power factor 0.85 uses about 5,889 W. A 2,000 W heater on 230 V draws about 8.7 A.

For the relationships with resistance, use the Ohm's law calculator. Size cable runs with the voltage drop calculator, and estimate running costs with the electricity cost calculator.

How to use the Watts Volts Amps Calculator

  1. Choose the circuitDC, single-phase AC or three-phase AC.
  2. Choose what to findWatts, amps or volts.
  3. Enter the other two valuesAdd the power factor for AC loads if you know it.
  4. Read the resultsSee watts, amps, volts, volt-amperes and kilowatts.

Watts Volts Amps Calculator features

  • Watts, volts and amps in any direction
  • DC, single-phase and three-phase AC
  • Power factor for AC loads
  • Apparent power in VA and kVA
  • Equivalent resistance for DC
  • Formulas shown
  • Free and instant

Common uses

  • Sizing fuses, breakers and extension leads
  • Checking appliance current draw
  • Generator and inverter sizing
  • Motor and workshop wiring
  • Solar and battery systems

Watts, volts and amps in practice: air conditioners, UPS and generator ratings, breakers and solar panels

By the FreeToolsWorld editorial team · Updated November 2026 · How we write and check our guides

Converting between watts, volts and amps answers the questions people ask when buying appliances, sizing a UPS or generator, choosing a breaker or wiring solar panels. The relationships are simple for heaters and kettles, but motors and electronics add power factor, which explains why UPS and generators are rated in VA or kVA. This guide works through household and solar examples relevant to homes in Pakistan.

A worked example: an air conditioner

A 1.5-ton inverter air conditioner might draw around 1,500 to 1,800 W while running at full output. On a 230 V supply, that is roughly 6.5 to 8 A. Conventional, non-inverter units draw a large surge when the compressor starts, briefly several times the running current, which can trip weak breakers or overload a small generator. Checking the running and starting current on the specification sheet helps choose wiring and backup equipment.

UPS and generator ratings

Backup equipment is often rated in volt-amperes rather than watts. A UPS rated at 1,000 VA with a power factor of 0.8 can supply about 800 W of real power. A 5 kVA generator at a power factor of 0.8 supplies about 4 kW. Adding up the watts of everything you want to run, then choosing equipment with a comfortable margin, avoids overloads when several appliances switch on together.

Power factor

For heaters, kettles and filament bulbs, watts equal volts times amps. Motors, compressors and many electronic devices draw current that is out of step with the voltage, so the real power is volts times amps times the power factor. Industrial consumers with low power factors may face penalties on their electricity bills and often install capacitor banks to correct it.

Breakers and wiring

A 2,300 W heater on 230 V draws 10 A. Circuits are protected by breakers rated for the cable, commonly 6 or 10 A for lighting, 16 or 20 A for sockets and larger ratings for air conditioners and water heaters. Many electricians avoid loading a circuit continuously beyond about 80% of its breaker rating, leaving a margin for safety.

Small loads

Small devices draw little current: a 12 W LED bulb at 230 V draws about 0.05 A, and a phone charger even less. Leaving them on costs little in power, though many small loads together add up over a month. Knowing which loads are large, such as heaters, irons, air conditioners and water pumps, focuses efforts to save energy.

Solar panels

A typical modern solar panel rated at 550 W produces its maximum power at around 41 V, which is about 13.4 A. Connecting panels in series raises the voltage while keeping the current the same, which keeps cable losses low. Inverters and charge controllers have maximum voltage and current limits, so installers calculate panel arrangements carefully to stay within them.

Three-phase supplies

Large homes, commercial buildings and factories often use three-phase supplies, which deliver more power with less current per conductor. Power on a balanced three-phase system is about 1.73 times the line voltage times the current times the power factor. Distribution companies usually require three-phase connections above a certain sanctioned load.

Energy versus power

Watts measure power, the rate of using energy, while kilowatt-hours measure energy over time. A 2,000 W heater running for three hours uses 6 kWh. Electricity bills charge for energy, so reducing the hours a high-power appliance runs saves more than worrying about small standby loads.

Common mistakes

  • Treating VA ratings as watts for motors and electronics.
  • Ignoring the starting surge of compressors and pumps.
  • Overloading circuits with several high-power appliances.
  • Confusing kW with kWh.

Related tools

For voltage, current and resistance, use Ohm's Law Calculator. To estimate running costs, try Electricity Cost Calculator, and for long cable runs, Voltage Drop Calculator.

Sanctioned load

Electricity connections in Pakistan have a sanctioned load, the maximum demand agreed with the distribution company, shown in kilowatts on the bill. Adding several air conditioners or an electric vehicle charger may push demand above it. Applying for an increase keeps the connection compliant and avoids problems with the meter or supply.

Electric vehicle charging

A home charger for an electric car might draw 3.7 kW on a single-phase supply, about 16 A at 230 V, for several hours. Faster home chargers of 7 kW or more usually need a dedicated circuit and sometimes a three-phase supply. Checking the wiring and sanctioned load before installing a charger avoids overloads.

Choosing a UPS for load-shedding

To choose a UPS, list the devices you want to run during load-shedding, add up their watts and allow a margin of about a quarter. Fans, lights, a router and a television together may need only 300 to 500 W, while an air conditioner or refrigerator needs a much larger system. Battery capacity then decides how long that load can run.

Limits

The calculator uses standard formulas. Wiring and equipment choices should follow local regulations and be checked by a qualified electrician.

Frequently asked questions

How do I convert watts to amps?

For DC, amps = watts ÷ volts. For single-phase AC, amps = watts ÷ (volts × power factor). A 1,200 W microwave on 120 V with a power factor of 1 draws 10 A.

How do I convert amps to watts?

Multiply volts by amps, and by the power factor for AC: W = V × A × PF. A 230 V appliance drawing 4 A at power factor 1 uses 920 W.

What is power factor?

The ratio of real power, in watts, to apparent power, in volt-amperes. Resistive loads have a power factor of 1; motors and electronics are lower because their current is out of step with the voltage.

How is three-phase power calculated?

With line-to-line voltage, P = √3 × V × I × PF. A 400 V three-phase load drawing 20 A at power factor 0.9 uses about 1.732 × 400 × 20 × 0.9 ≈ 12.5 kW.

What is the difference between watts and VA?

Watts measure real power that does work or makes heat; volt-amperes measure apparent power, voltage times current. They are equal only when the power factor is 1. UPS units and generators are rated in VA or kVA.

How many amps does a 2,000 W heater draw?

About 8.7 A on 230 V, or about 16.7 A on 120 V. That is why high-power appliances in North America often need dedicated circuits.

How many watts can a 13 A or 15 A circuit supply?

At 230 V, 13 A supplies about 2,990 W; at 120 V, a 15 A circuit supplies 1,800 W, and continuous loads are usually limited to 80% of that, about 1,440 W.

Do I use RMS voltage for AC?

Yes. Mains voltages such as 120 V and 230 V are already RMS values, so they go straight into the formulas. Peak voltage is about 1.414 times higher.